1. Copper or Aluminum conductor
2. PVC Insulation
3. PVC Sheath
Nominal area of Conductor | Thickness of Insulation | Unarmored Cable | Armoured Cable | ||||||
---|---|---|---|---|---|---|---|---|---|
Thickness of Sheath | Approx. overall diameter | Thickness of Bedding | Nominal armour wire diameter | Thickness of Over Sheath | Approx. Overall diameter | ||||
Extruded | Lapped | Extruded bedding | Lapped bedding | ||||||
mm2 | mm | mm | mm | mm | mm | mm | mm | mm | mm |
1.5 2.5
4 6 10
16 25 35
50 70 95
120 150 185
240 300 400 |
0.6 0.7
0.8 0.8 1.0
1.0 1.2 1.2
1.4 1.4 1.6
1.6 1.8 2.0
2.2 2.4 2.6 |
- -
- - 1.8
1.8 1.8 1.8
1.8 1.9 2.0
2.1 2.2 2.4
2.5 2.7 2.9 |
- -
- - 16.1
18.6 18.4 20.1
22.8 22.5 29.3
31.8 35.1 39.1
43.9 48.7 54.2 |
0.8 0.8
0.8 0.8 0.8
0.8 1.0 1.0
1.0 1.0 1.2
1.2 1.2 1.4
1.4 1.6 1.6 |
0.8 0.8
0.8 0.8 0.8
0.8 0.8 0.8
0.8 0.8 0.8
0.8 0.8 0.8
0.8 0.8 0.8 |
0.9 0.9
0.9 0.9 1.25
1.25 1.6 1.6
1.6 1.6 2.0
2.0 2.0 2.5
2.5 2.5 2.5 |
1.3 1.4
1.4 1.5 1.6
1.6 1.7 1.8
1.9 1.9 2.1
2.2 2.3 2.4
2.5 2.7 2.9 |
11.7 13.1
15.1 16.5 20.1
21.9 23.0 24.9
27.8 30.4 35.5
38.0 41.3 46.4
51.2 56.4 61.9 |
11.7 13.1
15.1 16.5 20.1
21.9 22.6 24.5
27.4 30.0 34.7
37.2 40.5 45.2
50.0 54.8 60.3 |
Size up to 10mm2 are manufactured with copper conductor only.
1. Copper or Aluminum conductor
2. PVC Insulation
3. PVC Bedding
4. Steel Wire Armouring
5. PVC Sheath
Nominal area of Conductor | Thickness of Insulation | Unarmored Cable | Armoured Cable | ||||||
---|---|---|---|---|---|---|---|---|---|
Thickness of Sheath | Approx. overall diameter | Thickness of Bedding | Nominal armour wire diameter | Thickness of Over Sheath | Approx. Overall diameter | ||||
Extruded | Lapped | Extruded bedding | Lapped bedding | ||||||
mm2 | mm | mm | mm | mm | mm | mm | mm | mm | mm |
1.5 2.5 1.5 2.5
4 6 10
16 25 35
50 70 95
120 150 185
240 300 400 |
0.6 0.7 0.6 0.7
0.8 0.8 1.0
1.0 1.2 1.2
1.4 1.4 1.6
1.6 1.8 2.0
2.2 2.4 2.6 |
- - - -
- - 1.8
1.8 1.8 1.8
1.8 1.9 2.1
2.2 2.3 2.5
2.6 2.8 3.1 |
- - - -
- - 17.0
19.7 20.4 22.4
25.5 28.7 33.3
36.3 40.0 44.6
50.1 55.6 62.2 |
0.8 0.8 0.8 0.8
0.8 0.8 0.8
0.8 1.0 1.0
1.0 1.2 1.2
1.2 1.4 1.4
1.6 1.6 1.6 |
0.8 0.8 - -
0.8 0.8 0.8
0.8 0.8 0.8
0.8 0.8 0.8
0.8 0.8 0.8
0.8 0.8 0.8 |
0.9 0.9 0.9 0.9
0.9 1.25 1.25
1.25 1.6 1.6
1.6 2.0 2.0
2.0 2.5 2.5
2.5 2.5 2.5 |
1.4 1.4 1.4 1.4
1.4 1.5 1.6
1.6 1.7 1.8
1.9 2.0 2.1
2.2 2.4 2.5
2.6 2.8 3.0 |
12.3 13.6 12.8 14.1
15.8 18.0 21.2
23.1 25.0 27.3
30.5 35.0 39.3
42.2 47.5 51.9
57.8 63.2 69.6 |
12.3 13.6 - -
15.8 18.0 21.2
23.1 24.6 26.9
30.1 34.2 38.5
41.4 46.3 50.7
56.2 61.6 68.0 |
Size up to 10mm2 are manufactured with copper conductor only.
Copper or aluminum Conductor with reduced neutral Conductor P.V.C Insulated P.V.C Sheathed. Un-armoured and Armoured Cables.
Single Layer of Galvanized Steel Wire.
Red, Yellow, Blue and Black
Black or Customers Choice
Nominal area of Conductor | Nominal area of neutral conductor | Thickness of insulation phase conductor | Thickness of insulation neutral conductor | Un-armoured Cables | Armoured Cables | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Thickness of sheath | Approx. Overall diameter | Thickness of Bedding | Nominal armour wire diameter | Thickness of over Sheath | Approx. Overall Diameter | ||||||
Extruded | Lapped | Extruded Bedding | Lapped Bedding | ||||||||
mm2 | mm2 | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm |
25 35 50 70 95 120 150 185 240 300 300 400 |
16 16 25 35 50 70 70 95 120 150 185 185 |
1.2 1.2 1.4 1.4 1.6 1.6 1.8 2.0 2.2 2.4 2.4 2.6 |
1.0 1.0 1.2 1.2 1.4 1.4 1.4 1.6 1.6 1.8 2.0 2.0 |
1.8 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.7 2.9 2.9 3.2 |
22.9 24.7 28.3 32.0 37.5 41.4 44.7 49.9 56.0 62.2 64.2 69.6 |
1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.4 1.6 1.6 1.6 1.8 |
0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 |
1.6 1.6 1.6 2.0 2.0 2.5 2.5 2.5 2.5 2.5 2.5 3.1 |
1.8 1.8 1.9 2.0 2.2 2.3 2.4 2.5 2.7 2.9 2.9 3.15 |
27.8 29.5 33.1 38.0 43.7 49.0 52.0 57.2 63.7 69.8 71.8 78.6 |
27.4 29.1 32.7 37.2 42.9 47.8 50.8 56.0 62.1 68.2 70.2 76.6 |
* Circular Solid Conductors (class 1)
+ Circular and Circular Compacted Standed Conductors (class 2)
1. Copper or Aluminum conductor
2. PVC Insulation
3. PVC Bedding
4. Steel Wire Armouring
5. PVC Sheath
Nominal area of Conductor | Thickness of Insulation | Unarmored Cable | Armoured Cable | ||||||
---|---|---|---|---|---|---|---|---|---|
Thickness of Sheath | Approx. overall diameter | Thickness of Bedding | Nominal armour wire diameter | Thickness of Over Sheath | Approx. Overall diameter | ||||
Extruded | Lapped | Extruded bedding | Lapped bedding | ||||||
mm2 | mm | mm | mm | mm | mm | mm | mm | mm | mm |
1.5 2.5
4 6 10
16 25 35
50 70 95
120 150 185
240 300 400 |
0.6 0.7
0.8 0.8 1.0
1.0 1.2 1.2
1.4 1.4 1.6
1.6 1.8 2.0
2.2 2.4 2.6 |
- -
- - 1.8
1.8 1.8 1.8
1.9 2.0 2.2
2.3 2.5 2.6
2.8 3.1 3.3 |
- -
- - 18.6
21.6 22.9 25.4
29.2 33.0 38.3
41.8 46.3 51.3
58.0 64.6 72.0 |
0.8 0.8
0.8 0.8 0.8
0.8 1.0 1.0
1.2 1.2 1.2
1.4 1.4 1.6
1.6 1.6 1.8 |
0.8 0.8
0.8 0.8 0.8
1.0 0.8 0.8
0.8 0.8 0.8
0.8 0.8 0.8
0.8 0.8 0.8 |
0.9 0.9
1.25 1.25 1.25
1.6 1.6 1.6
2.0 2.0 2.0
2.5 2.5 2.5
2.5 2.5 3.15 |
1.4 1.4
1.5 1.5 1.6
1.7 1.8 1.9
2.0 2.1 2.2
2.4 2.5 2.6
2.8 3.0 3.3 |
13.0 14.5
17.8 19.0 22.8
26.3 27.8 30.5
35.4 39.2 44.3
49.3 53.6 59.0
65.7 72.0 81.3 |
13.0 14.5
17.8 19.2 22.8
25.9 27.4 30.1
34.6 38.4 43.5
48.1 52.4 57.4
64.1 70.4 79.3 |
Size up to 10 mm² are manufactured with copper conductor only.
Size up to 35 mm² are manufactured with either circular or shaped conductors